Saturday, November 1, 2008

All done!


The unit is in, the duct work completed and we fired it up. Pretty amazing to have the vents right on each cold isle. I'll write more later but after measuring the power usage, it uses 9Amps at 208volts. This is lower than we originally expected. This is in full economization mode. When the first compressor is on, it goes to only 30Amps. Our current Leibert was using over 58Amps so even if we were using one compressor 24/7, we cut our cooling usage in 1/2. For the last few days, we've been at full economization from about 6pm to 9am. I'll include a full range of pictures this soon.